Extractor Fan Ratings: Litres/Sec by Room | Kent Traders

A landlord replaced a failed bathroom extractor fan with whatever unit looked closest to the old one on a shelf, and the property still failed its damp inspection six months later, because the replacement moved less than half the air the room actually needed.

Quick Answer

Building Regulations Part F sets minimum extraction rates by room type: 15 litres per second for a bathroom or shower room, 30 l/s for a cooker hood mounted directly over a hob, and 60 l/s for a kitchen extractor fan mounted elsewhere in the room. Matching the fan to the room, not just the hole it needs to fit, is what actually clears moisture and prevents mould.

Browse Fan Isolator Switches at Trade Prices →

What Extraction Rate Does Each Room Actually Need?

Approved Document F sets a minimum litres-per-second (l/s) figure for each room type, based on how much moisture and airborne pollutant that room typically generates. A fan rated below the minimum for its room will technically run and technically extract air, it just won't do it fast enough to stop condensation and mould building up over time.

Room Type Minimum Extraction Rate Notes
Bathroom / shower room 15 l/s (intermittent) Continuous systems can run lower, around 8 l/s, since they operate constantly rather than in bursts
Kitchen, hood over hob 30 l/s Lower rate accepted because the hood captures pollutants directly at the source
Kitchen, fan elsewhere in room 60 l/s Higher rate compensates for the fan being further from where cooking fumes are generated
Utility room 30 l/s Same principle as a kitchen without a cooker present
The number on the box isn't always in l/s. Some manufacturers list extraction rate in m3/h (cubic metres per hour) instead. To convert, multiply l/s by 3.6 to get m3/h, or divide m3/h by 3.6 to get l/s. A fan advertised as "90 m3/h" is roughly 25 l/s, comfortably above the 15 l/s bathroom minimum but nowhere near the 60 l/s a kitchen fan away from the hob would need.

Why Doesn't a Bathroom Fan Just Work in a Kitchen?

The room types generate very different volumes of airborne moisture and grease, and the extraction rate is set accordingly. A bathroom produces steam in short, intense bursts, typically during a shower, so a 15 l/s fan running on a timer for a set period afterward is enough to clear it. A kitchen produces steam, grease particles and combustion by-products continuously while cooking, over a longer period and at a higher volume, which is why the minimum jumps to 30 or 60 l/s depending on where the fan sits relative to the hob.

Bathroom
15 l/s minimum

Short, intense moisture bursts from showering. A timer-controlled fan running for a set period after use is the standard approach.

Kitchen (hood over hob)
30 l/s minimum

Captures grease and moisture at the source, which is why the required rate is lower than a fan mounted elsewhere in the room.

Kitchen (fan elsewhere)
60 l/s minimum

Further from the hob means less efficient capture, so the fan has to move significantly more air to compensate.


What Should You Check Before Buying a Replacement Fan?

Fitting like-for-like on the assumption that the old fan was correctly specified in the first place is a common mistake, particularly in older properties or ones that have changed use over time, such as a bedroom converted into an en-suite. A few checks are worth running before ordering:

  • Confirm the room type and its minimum extraction rate from the table above, rather than assuming the old fan was sized correctly.
  • Check the l/s or m3/h figure on the new fan's specification, converting between the two if the manufacturer only lists one.
  • Factor in duct length and bends: a long or heavily bent duct run reduces the effective extraction rate below the fan's rated figure, so oversizing slightly is often sensible on longer runs.
  • Match the fan's IP rating to its bathroom zone if it's going in a bathroom, separately from checking its extraction rate.

Replacing an extractor fan also means checking the isolator switch. BS 7671 requires a 3-pole isolator for timer and run-on fans, and a standard light switch won't do the job.

Shop Fan Isolator Switches →

Does a More Powerful Fan Just Solve the Problem?

Not automatically. A fan rated well above the room's minimum can be noisier than necessary and, in some cases, pull air through gaps and under doors in a way that creates draughts rather than solving ventilation properly. The goal is matching the fan to the room's actual minimum requirement, with a reasonable margin for duct losses, rather than buying the highest-rated unit available on the assumption that more is always better. For a broader look at how bathroom electrical accessories are specified by zone, our fan isolator switch guide covers the isolation side of the same job in more depth.

Frequently Asked Questions

Building Regulations Part F sets a minimum of 15 litres per second for a bathroom or shower room on an intermittent system, meaning one that runs on a timer during and after use. A continuous system, which runs at a lower rate constantly rather than in bursts, can operate at around 8 l/s instead.
Kitchens generate more moisture, grease and combustion by-products over a longer period than a bathroom's short burst of steam from showering. A cooker hood mounted directly over the hob needs a minimum of 30 l/s because it captures pollutants at the source, while a fan mounted elsewhere in the kitchen needs 60 l/s to compensate for being further from where the fumes are produced.
Divide the m3/h figure by 3.6 to get litres per second, or multiply l/s by 3.6 to get m3/h. A fan rated at 90 m3/h converts to 25 l/s, which meets a bathroom's 15 l/s minimum comfortably but would fall short of a kitchen fan's 60 l/s requirement if mounted away from the hob.
You can, but a fan rated well above the room's requirement isn't automatically better. Oversizing can increase noise and, in some installations, create draughts by pulling more air through gaps and under doors than the room needs. Matching the fan to the room's minimum rate, with a reasonable allowance for duct losses, is generally the better approach than maximising power.
Yes. A fan's rated extraction figure is measured under test conditions, and a long or heavily bent duct run adds resistance that reduces the real-world airflow below that rating. On installations with a long duct run, choosing a fan rated somewhat above the room's minimum requirement helps ensure the actual delivered airflow still meets it.
Yes. Once a room contains a shower, bath, or basin used for washing, it falls under the bathroom ventilation requirement of 15 l/s minimum, regardless of what the room was originally used for. A change of use like this is also likely to be notifiable Building Regulations work, so it is worth confirming the full requirements before fitting the fan rather than treating it as a simple like-for-like swap.

Isolate Every Extractor Fan Correctly

BG fan isolator switches, 3-pole, 10A, in stock across every current finish. Trade pricing, fast UK dispatch.

Shop Fan Isolator Switches →
Previous articleGU10, B22 or E27? UK Lamp Fittings Explained | KT All articles Next articleSchool & Classroom Electrical Spec Guide | Kent Traders

RELATED ARTICLES

UK hotel room power load
Hotel Room Power Load: Kettle, Hair Dryer and Iron on One Socket?

A hotel guest room puts a kettle, a hair dryer and sometimes an iron within reach of the same sockets, and a 13A socket...

Astroflame fire door hinge
Fire Door Hinge Pads and Lock Kits: What Needs Protecting

A fire door is tested as a complete assembly, so every hinge recess and lock mortice cut into the leaf has to be protected...

Fire stopping pipe penetration
Fire Stopping Pipe Penetrations in HMOs and Hotels

A pipe through a fire-separating wall or floor is a hole in the fire rating unless it is sealed properly. This guide explains fire...

coshh for carpet cleaning
COSHH for Carpet Cleaning Chemicals in Hotels and HMOs

Carpet cleaning looks harmless until an inspector asks for the paperwork. This guide sets out what COSHH expects for carpet cleaning chemicals in hotels...

Which Shower for your water system
Which Shower for Your Water System? Combi, Tank or Unvented

The same shower can feel superb in one house and weak in the next, and the water system is almost always the reason. This...

Legionaire's Disease
Legionella Flushing for Empty Hotel and HMO Rooms

Empty hotel rooms and HMO bedrooms are where stagnant water collects, and stagnant water is where Legionella bacteria can multiply. This guide sets out...

Hard Water Uk
Hard Water in Hotels: Why Limescale Kills Kettles and Irons

Hard water carries dissolved calcium and magnesium, and heat turns them into limescale on kettle elements, iron soleplates and shower heads. This plain-English guide...

Electric Shower
Electric Shower kW Guide: 8.5, 9.5 or 10.5kW Compared | KT

Which electric shower kW rating do you need? For most homes 9.5kW is the sensible default, but the right answer depends on flow, winter...

Intumescent  strip size
Intumescent Strip Size for Fire Doors: 10, 15 or 20mm? | KT

Which intumescent strip size does your fire door need? Most 30-minute doors take 15mm x 4mm and most 60-minute doors take 20mm x 4mm...

trickle vents
Trickle Vents and Part F: Sizes for Replacement Windows | KT

Do replacement windows need trickle vents? In England, Part F of the Building Regulations says yes in most cases. New vents must match the...

Astro window restrictors
Window Restrictors: The 100mm Rule for Hotels, HMOs | KT

Window restrictors limit how far a window opens, usually to no more than 100mm, so a child or vulnerable adult cannot fall out. HSE...

Part m threshold
Part M Door Thresholds: The 15mm Rule Explained Simply | KT

Approved Document M Volume 2 wants entrance thresholds level, and where a raised one cannot be avoided it caps the total height at 15mm....

Fire blanket
Fire Blankets for Hotel and HMO Kitchens: What to Buy | KT

A fire blanket is the simplest piece of kitchen fire equipment, but only if the right size is mounted where staff can reach it....

Torch vs Emergency lighting
Hotel Room Torches vs Emergency Lighting: What Counts | KT

Home Office guidance lets the smallest B&Bs and guest houses in England rely on bedroom torches instead of fixed escape lighting. There is a...

Standard letterbox
Why a Standard Letterbox Voids Your Fire Door Rating | KT

A standard letterbox cut into an FD30 fire door is one of the most commonly missed compliance failures on a fire door inspection, and...

Closed vs concealed cistern
Concealed vs Close-Coupled Cisterns: Which for HMO? | KT

Landlords specifying cisterns for an HMO refurb usually pick on looks alone, and that's exactly where it goes wrong. A concealed cistern behind a...

Shop products from this guide