Electric Shower kW Guide: 8.5, 9.5 or 10.5kW Compared | KT

By Kent Traders Team · Updated 13 Oct 2026 · 6 min read · England

The electric shower kW rating decides how much cold mains water the unit can warm, not how hot the shower feels. Pick too small and winter showers run weak. Pick too big and you may need a bigger breaker. For most homes, 9.5kW is the sensible default.

Quick answer: Choose 9.5kW for most homes. It gives about 3.9 litres a minute at 37 degrees from 5 degree winter water on a 40A circuit, per the Aqualisa eVolve datasheet. Pick 10.5kW for a stronger winter flow if the board can take a 45 or 50A breaker, and 8.5kW only where supply is limited.

3.89 l/min9.5kW flow at 37 degrees from 5 degree water
40AMCB for the 8.5kW and 9.5kW eVolve
0.85 barMinimum mains pressure for the eVolve

Which electric shower kW rating do you need?

Choose 9.5kW for most homes, 10.5kW where the mains water is cold and the flow is generous, and 8.5kW only where the electrical supply cannot take more. The kW figure is heating power. It decides how much water the unit can warm, not how hot the shower feels.

Rating Current at 240V MCB (Aqualisa datasheet) Price from (13 Oct 2026)
8.5kW about 35A 40A £310.38
9.5kW about 40A 40A £321.54
10.5kW about 44A 45 to 50A £332.69

Those are Aqualisa eVolve units in white and satin silver on the electric showers page. Current is power divided by voltage, so it is our sum rather than a datasheet figure. The cost of moving from 8.5kW to 10.5kW is £22.31 on the unit, but the circuit has to carry it.

Why a higher kW rating does not always mean a hotter shower

A shower is a heater that warms a stream of water, so power, flow and temperature rise are locked together. Each litre per minute needs about 4.19kW to warm it by 60 degrees, and the useful rule is: temperature rise equals roughly 14.3 times the kW, divided by the flow in litres per minute.

A 9.5kW unit at 4 litres a minute could lift the water by about 34 degrees in theory. At 6 litres a minute it manages only about 23. The same shower feels hot or lukewarm purely because of the flow.

Aqualisa eVolve maximum flow at 37C with 5C winter water (power setting 3) Flow at 37C shower, 5C winter water (litres per minute)8.5kW3.489.5kW3.8910.5kW4.30Source: Aqualisa eVolve datasheet, power setting 3. Bars to scale.
More kW lets the unit run more water at the same temperature. Datasheet flows, not a promise for your supply.

Trade tip: When a customer says the shower is not hot enough, ask about the season before you ask about the unit. Winter mains water can be 10 degrees colder than summer, which costs the unit a third of its headroom.

How much water can each eVolve heat?

Aqualisa publishes maximum flow rates for each eVolve by inlet temperature. At 37°C and the top power setting, the 9.5kW unit delivers 3.89 litres a minute from 5°C winter water and 5.69 from 15°C summer water. Those figures run about 10 percent below the ideal sum, which allows for real losses.

Shower at 37°C 5°C inlet 10°C inlet 15°C inlet
8.5kW 3.48 l/min 4.13 l/min 5.09 l/min
9.5kW 3.89 l/min 4.62 l/min 5.69 l/min
10.5kW 4.30 l/min 5.11 l/min 6.28 l/min

Turn the dial up to 43°C and every figure falls. The 9.5kW drops to 3.78 litres a minute from 10°C water. Lower power settings fall further, down to 2.34 litres a minute in the table. The unit never gets hotter, it just gets slower.

Worked example: a winter en-suite

A landlord fits a shower to an HMO en-suite. Winter mains arrives at 10°C and tenants want 37°C. The datasheet gives the options below, and the pressure at the tap decides which is a fit.

Unit Max flow at 10°C inlet In practice Verdict
8.5kW 4.13 l/min Gentle, fine for a small head Fine if the circuit is limited
9.5kW 4.62 l/min Comfortable all year Best default
10.5kW 5.11 l/min Strongest, stays warm on cold nights Needs the larger MCB

When the mains is colder than the table assumes, the unit holds the temperature by cutting the flow. The tenant sees a weaker shower, not a colder one.

What the supply has to deliver first

Check the circuit and the water before you check the kW. Aqualisa lists the eVolve at 0.85 bar minimum pressure, with 1 bar recommended and 3 bar as the recommended maximum. It runs on a mains cold feed only, so a tank-fed supply needs a different product.

The circuit is the second limit. The datasheet specifies a 40A MCB on the 8.5kW and 9.5kW and 45 or 50A on the 10.5kW. The cable depends on the length and the installation method, so your electrician sizes it under BS 7671 from the instructions.

  1. Measure mains pressure and flow at the point the shower will connect.
  2. Confirm the supply to the board can carry the chosen circuit alongside the rest of the property.
  3. Match the MCB to the datasheet, then size the cable for the run.
  4. Fit a dedicated circuit, and check whether the work is notifiable.

In England a new circuit is usually notifiable under Part P, so use a registered electrician or involve building control. Approved Document P explains when notification is required. Wales, Scotland and Northern Ireland follow their own rules.

Where shower kW choices go wrong

  • Buying for the label. Higher kW does not rescue a weak mains supply.
  • Ignoring winter. A unit that suits July can disappoint in January.
  • Undersized circuit. A 10.5kW on a 40A breaker will trip.
  • Tank-fed water. The eVolve needs a mains cold feed.
  • Forgetting the head. A wide rain head spreads the flow thin, so the shower feels cold.

What to buy: Aqualisa eVolve and alternatives

The eVolve comes in white, grey or black with satin silver in all three ratings, and Aqualisa gives a 2 year warranty. It has a digital temperature display, three spray patterns and automatic phased shutdown to reduce limescale. Browse the full Aqualisa showering range for the rest of the family.

If the mains cannot support an electric unit, a mixer is the answer. The shower valves collection covers thermostatic options.

  • Mains pressure and flow measured, not guessed
  • Winter inlet temperature allowed for
  • MCB and cable matched to the datasheet and the run
  • Rating chosen from the flow table, not the label
  • Colour matched to the room: white, grey or black
  • Delivery allowed for: direct from the supplier, usually 3 to 5 working days

FAQs

For most homes a 9.5kW shower is the sensible default. It gives a comfortable flow in winter on a 40A circuit. Go to 10.5kW where the mains flow is strong and the board can carry a 45 or 50A breaker, and drop to 8.5kW only where the supply is limited.

No. Both heat the water to the same temperature. The 10.5kW can heat more water to that temperature, so it holds the flow better in winter. Aqualisa lists 4.30 litres a minute at 37 degrees from 5 degree water for the 10.5kW, against 3.48 for the 8.5kW.

Colder incoming water needs more heat to reach the set temperature. The unit has a fixed power, so it cuts the flow to compensate. On a 9.5kW eVolve the maximum flow falls from 5.69 litres a minute at 15 degrees to 3.89 at 5 degrees at the top power setting.

Aqualisa specifies a 40A MCB for the 8.5kW and 9.5kW eVolve and 45 or 50A for the 10.5kW. Cable size depends on the run and the installation method, so a qualified electrician should size it under BS 7671. Never fit a bigger breaker than the instructions allow.

Aqualisa gives a minimum of 0.85 bar for the eVolve, with 1 bar recommended and a recommended maximum of 3 bar. It needs a mains cold supply, so it will not run from a gravity-fed tank. Measure the flow and pressure at the connection point before you order.

The plumbing is straightforward, but the circuit is not. In England a new circuit is usually notifiable under Part P, so it must be installed by a registered electrician or reported to building control. Approved Document P explains when notification is needed. Wales, Scotland and Northern Ireland have separate rules.

Choose your electric shower

Pick the rating from the flow table, match the breaker, then order the Aqualisa eVolve in one go.

Shop electric showers

Previous articleIntumescent Strip Size for Fire Doors: 10, 15 or 20mm? | KT All articles

RELATED ARTICLES

Intumescent  strip size
Intumescent Strip Size for Fire Doors: 10, 15 or 20mm? | KT

Which intumescent strip size does your fire door need? Most 30-minute doors take 15mm x 4mm and most 60-minute doors take 20mm x 4mm...

trickle vents
Trickle Vents and Part F: Sizes for Replacement Windows | KT

Do replacement windows need trickle vents? In England, Part F of the Building Regulations says yes in most cases. New vents must match the...

Astro window restrictors
Window Restrictors: The 100mm Rule for Hotels, HMOs | KT

Window restrictors limit how far a window opens, usually to no more than 100mm, so a child or vulnerable adult cannot fall out. HSE...

Part m threshold
Part M Door Thresholds: The 15mm Rule Explained Simply | KT

Approved Document M Volume 2 wants entrance thresholds level, and where a raised one cannot be avoided it caps the total height at 15mm....

Fire blanket
Fire Blankets for Hotel and HMO Kitchens: What to Buy | KT

A fire blanket is the simplest piece of kitchen fire equipment, but only if the right size is mounted where staff can reach it....

Torch vs Emergency lighting
Hotel Room Torches vs Emergency Lighting: What Counts | KT

Home Office guidance lets the smallest B&Bs and guest houses in England rely on bedroom torches instead of fixed escape lighting. There is a...

Standard letterbox
Why a Standard Letterbox Voids Your Fire Door Rating | KT

A standard letterbox cut into an FD30 fire door is one of the most commonly missed compliance failures on a fire door inspection, and...

Closed vs concealed cistern
Concealed vs Close-Coupled Cisterns: Which for HMO? | KT

Landlords specifying cisterns for an HMO refurb usually pick on looks alone, and that's exactly where it goes wrong. A concealed cistern behind a...

Downlight insulation
Loft Insulation Over Downlights: What Actually Stops Fires

A landlord had fire-rated downlights fitted throughout an HMO loft conversion, then two years later a contractor topping up the loft insulation buried every...

Hotel welcome trays
Hotel Welcome Trays: What Actually Needs PAT Testing | KT

A guest complained her room kettle kept tripping the socket, and maintenance found the element had been failing for weeks. Nobody had tested it...

illuminated mirror and shaver stock
Illuminated Mirrors & Shaver Sockets: What's Legal | KT

A landlord asked an electrician to wire a normal double socket behind an HMO bathroom's new illuminated mirror, and was refused on the spot....

Garden room electrics
Garden Room Electrics: What Cable Actually Goes In | KT

A homeowner ran a heavy-duty extension lead across the lawn to a new garden office, and it tripped the whole house's RCD every time...

Masterplug night light sockets
Night Light Sockets: Do You Need One or a Lamp? | KT

A homeowner upgraded from a 7kW to a 10.5kW shower and kept the existing 6mm cable, assuming a cable is a cable. Within weeks...

USB DESKTOP POWER OUTLET
Reception Desk Power & USB Charging: What to Spec | KT

A guesthouse fitted USB sockets throughout every guest room but left reception on its original two sockets, both already taken by the card machine...

Hotel coffee pod machines
Hotel Kettle or Pod Machine? What Guest Rooms Need | KT

A guesthouse swapped every room kettle for a pod machine and found the sachet-restocking bill roughly doubled while some guests complained they couldn't make...

stairwell and corridor lighting
Corridor & Stairwell Sensor Lighting Guide | Kent Traders

A guesthouse stairwell had a switch only at the bottom, and a guest missed the last two steps coming down in the dark. PIR-controlled...

Shop products from this guide