BS 7671 divides a bathroom into three zones, and the zone an accessory falls in determines what you can fit and to what IP rating. Zone 0 is the interior of the bath tub or shower basin — only IPX7-rated, extra-low-voltage (12V SELV) equipment designed for immersion belongs here. Zone 1 is the area directly above zone 0 up to 2.25m above the finished floor; it suits IP65-rated fittings such as enclosed downlights and a correctly rated extractor fan. Zone 2 extends 0.6m horizontally beyond zone 1 (and around a washbasin), and needs accessories rated at least IP44. Anywhere outside the zones still carries a splash risk, so light switches and spurs near a basin are commonly specified at IP44 too. Map these zones before you choose a single product — every later decision depends on it.
- Home
- Bathroom & Wet Room Electrical Products Buying Guide
Bathroom & Wet Room Electrical Products Buying Guide
Choosing electrical accessories for a bathroom or wet room is governed by BS 7671 (the IET Wiring Regulations), which divides the room into zones 0, 1 and 2 and sets a minimum IP rating for each. The core decisions are simple once you know the rules: keep standard 13A sockets out of the room, use IP-rated accessories appropriate to the zone, isolate fixed appliances with a ceiling pull-cord switch, and protect every circuit with a 30mA RCD. Because a bathroom is a 'special location', the work is notifiable under Building Regulations Part P and must be carried out or certified by a qualified electrician. This guide explains how to specify a compliant set of British General (BG) IP-rated accessories and shaver supply units with confidence.
Quick Decision Summary
Use this summary for fast procurement decisions before reviewing the full guidance below.
- Best for: Bathroom and wet-room refurbishments needing zone-correct, IP-rated accessories — IP65 fittings for zone 1, IP44 switches and spurs for zone 2, a shaver supply unit, an IP-rated extractor fan and a ceiling pull-cord isolator.
- Avoid if: You are wiring a dry room with no basin, bath or shower — ordinary unrated accessories are fine and the zone and IP rules below do not apply.
- Recommendation: Map the zones first, then match each accessory to its zone IP minimum, keep 13A sockets at least 3m from the zone 1 boundary, add a BG shaver supply unit for the exception, and have a qualified electrician complete and certify the notifiable work under Part P.
Key Points to Remember
Map the bathroom zones first (0, 1, 2)
BS 7671 splits the room into zone 0 (inside the bath or shower basin), zone 1 (above it to 2.25m) and zone 2 (0.6m beyond zone 1). The zone an accessory sits in fixes the minimum IP rating and what is permitted there.
Match the IP rating to the zone
Zone 0 needs IPX7 (immersion-proof); zone 1 needs IP65 or better against water jets; zone 2 and any splash-risk area outside the zones need IP44 minimum. Buy accessories marked to at least the zone's IP rating, never below.
No 13A sockets near the bath — shaver units are the exception
Standard 13A socket-outlets are not permitted within 3m horizontally of the zone 1 boundary. The only socket allowed is a shaver supply unit to BS EN 61558-2-5 with an isolating transformer, sited away from direct splashing.
Isolate locally and protect with a 30mA RCD
Switch fixed loads (fans, mirrors, heaters) with a ceiling pull-cord rather than a wall switch inside the zones, and protect all bathroom circuits with a 30mA RCD. Supplementary bonding may also be required where conditions are not met.
What are the bathroom zones in BS 7671?
Which IP rating do I need in each zone?
The IP (Ingress Protection) code has two digits: the first is protection against solids, the second against water — the higher the second digit, the more water protection. Match it to the zone. Zone 0 requires IPX7, meaning protection against temporary immersion. Zone 1 requires IP65 or better, giving full dust-tightness and protection against water jets, which is why enclosed IP65 downlights are the norm there. Zone 2 requires IP44 as a minimum — protection against solid objects over 1mm and water splashing from any direction. Outside the zones there is no mandatory IP rating, but where splashing is likely, such as a switch beside a washbasin, IP44 is sensible practice. Always buy to at least the zone's figure; a higher rating is acceptable, a lower one is not. BG offers IP-rated accessories suited to these splash and jet conditions.
Can I fit a normal 13A socket in a bathroom?
No — a standard 13A socket-outlet is not permitted within 3 metres horizontally of the boundary of zone 1, which rules it out of almost every domestic bathroom. The single exception is a shaver supply unit complying with BS EN 61558-2-5: it uses an isolating transformer so there is no direct connection to the mains supply, and it must be sited where it is unlikely to be splashed directly. In practice that means mounting it outside zone 2 wherever possible, away from the bath or shower. BG supplies dedicated shaver sockets and dual-voltage shaver supply units built to this standard, often combined with a mirror light or LED, which are the correct and compliant way to provide a charging point for razors and electric toothbrushes in a bathroom.
How do I light a bathroom and run an extractor fan safely?
Bathroom lighting and ventilation must match the zone they occupy. For ceiling and shower-area lights, choose enclosed IP65 downlights so they withstand the steam and water jets typical of zone 1; fittings in zone 2 should be at least IP44. Extractor fans must likewise be rated for their position — an IP-rated fan suited to zone 1 if mounted above the shower, with the right rating for the location elsewhere — and are commonly specified with a timer overrun or a humidistat so they clear moisture after use and reduce condensation. Switch lights and fans with a ceiling-mounted pull-cord inside the room rather than a wall switch in a zone, or place a wall switch outside the door. Heated demister mirrors are a popular addition: choose a zone-appropriate IP-rated mirror, wired on its own fused spur and isolated by a pull-cord, so the demister and lighting are safely controlled.
How should I switch and isolate bathroom circuits?
Inside the bathroom, the safest way to switch a light, fan or heater is a ceiling-mounted pull-cord switch, because it keeps the operator clear of any contact between a wall switch and wet hands. A common arrangement is a pull-cord for the main lighting and a separate fused connection unit, sited outside the zones, feeding fixed appliances such as the extractor fan or a heated mirror so each can be isolated for maintenance. BG manufactures ceiling pull-cord switches, including illuminated and double-pole versions, plus IP44 fused spurs and weatherproof grid units suitable for these duties. Where a wall switch is genuinely needed, keep it outside the zones or fit an IP-rated type with a cord. Plan isolation at the design stage so every fixed load can be safely switched off for cleaning or servicing without disturbing other circuits.
What about RCD protection, bonding and Part P?
Every circuit serving a bathroom must be protected by a 30mA residual current device (RCD), which disconnects the supply fast enough to protect against electric shock — this is a firm BS 7671 requirement for special locations. Supplementary equipotential bonding of exposed and extraneous metalwork may also be needed; it can be omitted only where all the standard's conditions are met (main bonding present, RCD protection on all circuits, and verified continuity), so it must be assessed on the specific installation rather than assumed. Critically, a bathroom is a 'special location', so the work is notifiable under Building Regulations Part P in England and Wales: it must be carried out, inspected and certified by a registered competent electrician, or notified to building control. Do not treat bathroom wiring as DIY — engage a qualified electrician for the design, installation and certification of the whole job.
Step-by-Step Guide
-
Map the zones in the room
Mark zone 0 (inside the bath/shower), zone 1 (above it to 2.25m) and zone 2 (0.6m beyond), and note the 3m no-socket boundary around zone 1.
-
Match each accessory to its zone IP rating
Specify IPX7 in zone 0, IP65 downlights and fans in zone 1, and IP44 switches and spurs in zone 2 or any splash-risk area near the basin.
-
Plan sockets, isolation and protection
Keep 13A sockets 3m from zone 1, add a BG shaver supply unit for charging, switch fixed loads with a pull-cord, and protect all circuits with a 30mA RCD.
-
Have a qualified electrician complete and certify
Because bathroom work is notifiable under Part P, have a registered electrician install, test and certify the circuits, including any supplementary bonding required.