Intumescent Strip Size for Fire Doors: 10, 15 or 20mm? | KT

By Kent Traders Team · Updated 10 Oct 2026 · 6 min read · England

An intumescent strip is the thin seal in the edge of a fire door frame that swells in heat and closes the gap. Buy the wrong size and the door can fail an inspection, even if it looks fine. Most 30-minute doors take 15mm x 4mm and most 60-minute doors take 20mm x 4mm, but your door label has the final say.

Quick answer: Match the strip to the door label. The BWF Fire Door Alliance says most modern 30-minute doors take a 15mm x 4mm strip, and most 60-minute doors take 20mm x 4mm or two 10mm x 4mm strips. Choose fire and smoke strip where smoke sealing is specified, and keep the gap to about 3mm.

15mmTypical strip width for a 30-minute door
20mmTypical strip width for a 60-minute door
3mmGap limit at the sides and head

Which intumescent strip size does a fire door need?

Match the strip to the door's fire rating and the door maker's specification. The BWF Fire Door Alliance says most modern 30-minute doors take a 15mm x 4mm strip, and most 60-minute doors take 20mm x 4mm or two 10mm x 4mm strips.

Door rating Typical strip Alternative Who decides
FD30 (30 minutes) 15mm x 4mm 10mm x 4mm only where the door maker allows it Door leaf manufacturer
FD60 (60 minutes) 20mm x 4mm Two 10mm x 4mm strips side by side Door leaf manufacturer
Existing door, groove already cut Same width as the groove Never force a wider strip in Door certificate or label

The BWF is blunt on one point: seals must be used as the door leaf manufacturer recommends. If the label or certificate says 15mm, a thicker strip is not extra safety. It is a deviation from the tested door.

Rule: The door maker’s certificate beats any size chart, including this one. Read the label on the door edge first.

Fire-only or fire and smoke: which strip do you need?

Fire-only strips swell in heat and close the gap. Fire and smoke strips do the same and add a brush or blade that blocks cold smoke before the heat arrives. The BWF notes that smoke seals are a Building Regulations requirement in some circumstances, so check your drawings, licence conditions or fire risk assessment.

Type What it does Sizes we stock Price (10 Oct 2026)
Fire only (Astro Strip FO) Expands in fire only 10, 15, 20, 25mm x 4mm £1.15 to £3.73
Fire and smoke, brush (FS) Fire seal plus brush for cold smoke 10, 15, 20, 25mm x 4mm £1.38 to £3.95
Fire and smoke, single or twin blade (SB, TB) Fire seal plus a flexible blade 10, 15, 20mm x 4mm £3.57 to £4.62

Every strip above is a 2.1m length from Astroflame. Fire-only is cheaper per length, but swapping it in where smoke sealing is specified fails the specification. Use the same seal type around the whole door, as the BWF advises.

How big can the gap be around a fire door?

Where intumescent strips go: both sides and the top, not the bottom Door leafStrip in frameGap about 3mmat sides and topNo strip acrossthe bottom edge
Strips go in the frame at the head and both sides. The bottom edge takes no strip. Not to scale.

A strip can only seal a gap it can bridge. The BWF says the gap should not exceed 3mm along the two long edges and across the top. Its installation guide gives the head and side gap as 2 to 4mm, so the door certificate sets the real tolerance.

The bottom gap is separate. The BWF puts it at around 10mm for non-smoke doors and 3mm where smoke seals are required, so check the manufacturer’s instructions.

Watch out: If the gap is wider than the strip can close, fix the door or frame first. Do not stack extra strips to cover a hung door that is out of true.

How to fit an intumescent strip to a fire door

  1. Read the door label or certificate for the rating, strip size and any smoke requirement.
  2. Measure the gap at the head and at three points down each side. Anything over 3mm needs fixing before you seal.
  3. Rout or confirm the groove in the frame so it matches the strip width. The BWF prefers frame fitting, with the door edge as the fallback.
  4. Cut strips so each run is uninterrupted across the head and down both sides, pressing the self-adhesive backing home.
  5. Close the door. It should latch without catching, and the strip should sit just proud of the groove.

A standard 1981mm x 838mm door needs about 4.8m of strip: two stiles at 1.98m and a head at 0.84m. That is three 2.1m lengths, with offcuts left over.

Trade tip: Fit strips after decoration, and do not paint over smoke seals unless the manufacturer says you can.

Worked example: an eight-door HMO

A landlord re-seals eight FD30 bedroom doors. Each door needs three 2.1m lengths, so the order is 24 lengths. These are the choices, priced from the Astroflame range.

Option Lengths Price each Total Verdict
15mm x 4mm fire only 24 £1.70 £40.80 Cheapest, no smoke seal
15mm x 4mm fire and smoke, brush 24 £1.91 £45.84 Best value where smoke sealing is needed
15mm x 4mm fire and smoke, single blade 24 £4.20 £100.80 Only if the spec calls for blade

The smoke option adds £5.04 for the whole house, which is why it is usually the sensible default for bedroom doors that open onto a corridor. For the same house in FD60, 20mm brush strip at £1.96 per length (white) costs £47.04 for 24 lengths.

Where strip jobs go wrong

  • Choosing by colour or price. Size and rating come from the door, and colour comes last.
  • Broken runs. The BWF wants uninterrupted strips, so butt-joining offcuts across a head is a fail.
  • Mixing seal types. Different cores react differently, so keep one type around the door.
  • Ignoring the gap. A strip cannot rescue a 6mm gap.
  • Painting the seal. Thick paint can stop a strip swelling.
  • Stripping the bottom. The bottom edge takes a threshold gap or a bottom seal, not a side strip.

What to buy: Astroflame strips and seals

Start with the intumescent fire seals range, which lists over 40 strips across every size above. If the door spec calls for smoke sealing, the fire and smoke seals collection groups the combined strips and door bottom seals.

  • Door rating and strip size copied from the label or certificate
  • Fire-only or fire and smoke decided from the specification
  • Lengths counted: three per standard door, five if you are fitting two 10mm strips per edge
  • Colour matched to the frame: white, brown, black, grey or red on fire-only
  • Delivery allowed for: dispatch direct from the supplier, usually within 3 to 5 working days

For the rest of the doorset, the Astroflame range also covers finger guards and wraps, collars and sleeves.

FAQs

Use the size on the door label or certificate. As a guide, the BWF Fire Door Alliance says most modern 30-minute doors take 15mm x 4mm and most 60-minute doors take 20mm x 4mm or two 10mm x 4mm strips. The door leaf manufacturer always has the final say.

On a 60-minute door the BWF lists two 10mm x 4mm strips as an accepted alternative to one 20mm x 4mm strip. Fit them only if the door maker specifies it. Two strips mean nearly double the lengths to buy, so check the price before you commit.

A fire-only strip swells in heat to close the gap. A fire and smoke strip adds a brush or blade that blocks cold smoke early. Smoke seals are a Building Regulations requirement in some circumstances, so confirm what your door specification needs before you buy the cheaper option.

Fit it in a groove in the frame along the head and both sides. The BWF prefers frame fitting, with the door edge as the fallback. Keep each run uninterrupted. The bottom edge takes no side strip, so it is left to a threshold gap or a bottom seal.

The BWF says the gap should not exceed 3mm along the long edges and across the top, and its installation guide quotes 2 to 4mm. The bottom gap is around 10mm for non-smoke doors and 3mm with smoke seals. The door certificate sets the true limits.

A standard 1981mm x 838mm door needs about 4.8m of strip, which is three 2.1m lengths. Fitting two 10mm strips per edge takes five lengths, because the two head strips share one. Count the lengths before you order, because a short run across the head is not acceptable.

Order your fire door seals

Work out the rating, size and smoke requirement, then order the matching Astroflame strips in one go.

Shop intumescent strips

Previous articleTrickle Vents and Part F: Sizes for Replacement Windows | KT All articles Next articleElectric Shower kW Guide: 8.5, 9.5 or 10.5kW Compared | KT

RELATED ARTICLES

Electric Shower
Electric Shower kW Guide: 8.5, 9.5 or 10.5kW Compared | KT

Which electric shower kW rating do you need? For most homes 9.5kW is the sensible default, but the right answer depends on flow, winter...

trickle vents
Trickle Vents and Part F: Sizes for Replacement Windows | KT

Do replacement windows need trickle vents? In England, Part F of the Building Regulations says yes in most cases. New vents must match the...

Astro window restrictors
Window Restrictors: The 100mm Rule for Hotels, HMOs | KT

Window restrictors limit how far a window opens, usually to no more than 100mm, so a child or vulnerable adult cannot fall out. HSE...

Part m threshold
Part M Door Thresholds: The 15mm Rule Explained Simply | KT

Approved Document M Volume 2 wants entrance thresholds level, and where a raised one cannot be avoided it caps the total height at 15mm....

Fire blanket
Fire Blankets for Hotel and HMO Kitchens: What to Buy | KT

A fire blanket is the simplest piece of kitchen fire equipment, but only if the right size is mounted where staff can reach it....

Torch vs Emergency lighting
Hotel Room Torches vs Emergency Lighting: What Counts | KT

Home Office guidance lets the smallest B&Bs and guest houses in England rely on bedroom torches instead of fixed escape lighting. There is a...

Standard letterbox
Why a Standard Letterbox Voids Your Fire Door Rating | KT

A standard letterbox cut into an FD30 fire door is one of the most commonly missed compliance failures on a fire door inspection, and...

Closed vs concealed cistern
Concealed vs Close-Coupled Cisterns: Which for HMO? | KT

Landlords specifying cisterns for an HMO refurb usually pick on looks alone, and that's exactly where it goes wrong. A concealed cistern behind a...

Downlight insulation
Loft Insulation Over Downlights: What Actually Stops Fires

A landlord had fire-rated downlights fitted throughout an HMO loft conversion, then two years later a contractor topping up the loft insulation buried every...

Hotel welcome trays
Hotel Welcome Trays: What Actually Needs PAT Testing | KT

A guest complained her room kettle kept tripping the socket, and maintenance found the element had been failing for weeks. Nobody had tested it...

illuminated mirror and shaver stock
Illuminated Mirrors & Shaver Sockets: What's Legal | KT

A landlord asked an electrician to wire a normal double socket behind an HMO bathroom's new illuminated mirror, and was refused on the spot....

Garden room electrics
Garden Room Electrics: What Cable Actually Goes In | KT

A homeowner ran a heavy-duty extension lead across the lawn to a new garden office, and it tripped the whole house's RCD every time...

Masterplug night light sockets
Night Light Sockets: Do You Need One or a Lamp? | KT

A homeowner upgraded from a 7kW to a 10.5kW shower and kept the existing 6mm cable, assuming a cable is a cable. Within weeks...

USB DESKTOP POWER OUTLET
Reception Desk Power & USB Charging: What to Spec | KT

A guesthouse fitted USB sockets throughout every guest room but left reception on its original two sockets, both already taken by the card machine...

Hotel coffee pod machines
Hotel Kettle or Pod Machine? What Guest Rooms Need | KT

A guesthouse swapped every room kettle for a pod machine and found the sachet-restocking bill roughly doubled while some guests complained they couldn't make...

stairwell and corridor lighting
Corridor & Stairwell Sensor Lighting Guide | Kent Traders

A guesthouse stairwell had a switch only at the bottom, and a guest missed the last two steps coming down in the dark. PIR-controlled...

Shop products from this guide