splash-img-tpt Skip to content
BG, Luceco & Masterplug orders over £50 qualify for free UK mainland delivery
BG, Luceco & Masterplug orders over £50 qualify for free UK mainland delivery

Astroflame PFP FR Acrylic - CE/UKCA (Foil - White 600ml)

Original price £5.04 - Original price £5.04
Original price
£5.04
£5.04 - £5.04
Current price £5.04

Astroflame PFP FR Acrylic - CE/UKCA (Foil - White 600ml)

Key Points:

  • High end formula, certified worldwide
  • Classified for fire sealing all types of construction and building service penetrations
  • Very high sound insulation
  • Low emissions - environmentally and user friendly
  • Simple to apply with a smooth surface finish
  • Permanently flexible will accommodate movement up to 12.5%
  • No priming necessary for application to most materials
  • Suitable for most surfaces, included concrete, masonry, steel, gypsum, glass, plastics and most non-porous surfaces
  • Hardens quickly, tack free after 1 hour (the fire performance specification of the joint filler has been derived when the joint filler has been let to cure for a month)
  • Extended to 24 months storage time (under correct conditions)

Description:

Designed to prevent the spread of fire and smoke through joints and openings in fire rated walls and floors (including openings formed around building service penetrations); the Astro PFP FR Acrylic will also maintain the acoustic design performance.

When subjected to atmospheric conditions, the sealant cures however, it will retain a degree of elasticity for joint movement. Under fire exposure, The Astro PFP FR Acrylic creates a robust fire seal by the formation of a durable intumescent char.

The Astro PFP FR Acrylic can be used with a suitable filling material i.e. stone wool or Astro PFP FR backing material in order to secure correct width to depth ratio, and to reduce the shrinking of the sealant during curing. Minimum depth and maximum width of the joints are included in the installation instructions.

When testing pipes, one can choose not to cap (or close) the pipe, or cap the pipe inside the furnace, or outside the furnace, or on both sides. The configuration chosen depends on the intended application of the pipe and/or the installation environment.

The code defining if a pipe is capped is stated after the fire classification. For instance, EI 60 C/U which means the pipe was capped inside the furnace, and uncapped outside the furnace. The test configuration defines the approvals possible.

Our engineering judgment based on EN 1366-3:2009 are:

Intended use of pipe Pipe end condition4
Rainwater pipe, plastic At drainage U/U 1)
Not at drainage C/C 2)
Drainage or sewage pipe, plastic Ventilated drain U/U 1)
Unventilated drain U/C 1)
Drain w/water trap U/C 1)
Not at drainage C/C 2)
Pipe in closed circuit (water, gas, air, electricity etc.) C/C 2) 3)
Flue gas recovery system pipe, plastic U/C 1)
Pipe with open ends and 50cm length on both sides, plastic U/U 2)
Pipe supported by suspension system, metal Fire rated support C/U 1)
Non-fire rated U/C 1)
Waste disposal shaft pipe, metal U/C 1)
1) Suggested in EN 1366-3:2009. 2) Astroflames's judgment based on tests. 3) Metal pipes should have fire rated support. 4) U/U classified fire seals cover C/U, U/C and C/C. C/U classified fire seals cover U/C and C/C. U/C classified fire seals cover C/C.

Specification:
  • Single Foil Pack - 600ml
  • Colour: White

Download and review any of the following information:

Certification/Fire Test Reports:

CE InformationCE Marked Documents
'DoP's are 'Declaration of Performance'
'CoC's are 'Certificate of Constancy of Performance'
'ETA' European Technical Assessment Sheet
'TDS' are 'Technical Data Sheet'
'UKTA' are UK Technical Assessment Sheet